Model Number |
LCFL-12 |
LCFL-15 |
LCFL-20 |
LCFL-25 |
LCFL-30 |
LCFL-40 |
LCFL-50 |
LCFL-60 |
||
|
refrigeration capacity |
kW |
35 |
44 |
58.5 |
69.0 |
86.0 |
116.0 |
140.0 |
168.0 |
|
|
10 ³ kcal/h |
30.1 |
37.8 |
50.3 |
59.3 |
74.1 |
100.0 |
120.0 |
145.0 |
||
|
power supply |
V/ph/Hz |
380/3/50 |
||||||||
|
Total power |
kW |
12.5 |
15.0 |
21.1 |
24.0 |
30.0 |
41.3 |
48.0 |
58.5 |
|
|
rated current |
A |
24.0 |
27.7 |
41.7 |
46.7 |
57.0 |
76.0 |
88.0 |
110.0 |
|
|
compressor |
type |
|
Vortex
|
|||||||
|
power |
KW |
10.1 |
12.5 |
17.4 |
20.2 |
25.0 |
34.8 |
40.6 |
50.0 |
|
|
water pump |
power |
KW |
1.2 |
1.2 |
2.2 |
2.2 |
2.2 |
3.5 |
3.5 |
4.0 |
|
head |
m |
29 |
27 |
27 |
26 |
25 |
34 |
29 |
25 |
|
|
water flow rate |
m³ /h |
6.0 |
7.6 |
10.0 |
11.8 |
14.8 |
20.0 |
24.0 |
28.9 |
|
|
L/min |
100 |
127 |
167 |
197 |
247 |
333 |
400 |
480 |
||
|
Water tank capacity |
L |
135 |
155 |
230 |
230 |
230 |
300 |
300 |
300 |
|
|
takeover size |
DN |
40 |
50 |
65 |
||||||
|
noise |
dB(A) |
65 |
66 |
67 |
68 |
68 |
69 |
69 |
69 |
|
|
unit weight |
kg |
340 |
415 |
620 |
670 |
780 |
1100 |
1300 |
1500 |
|
|
Overall dimensions |
long |
mm |
1510 |
1785 |
2080 |
2080 |
2080 |
2200 |
3000 |
3400 |
|
wide |
mm |
750 |
915 |
1050 |
1050 |
1050 |
1200 |
1200 |
1200 |
|
|
tall |
mm |
1480 |
1630 |
1820 |
1820 |
1910 |
2135 |
2120 |
2135 |
|
Product support is available for customization. Please contact us.